Single Acting Operating Principle and Conditions
Operating Principle

CCW
Input the compressed air from the A, the left and right plungers move reversely, the output pinion rotates counter-clockwise, and
the air at the sides of the both plungers exhausts from B.
CW
When it is out of air or power, the two plungers move to the center under the spring action, the output pinion rotates clockwise,
and the air exhausts from A.
Operating Conditions
1. Operating Media
Dry and clear air, or the non-corrosive gases
The maximum particle diameter must less than 40µm
2. Air Supply Pressure
The minimum supply pressure is 2.5Bar
The maximum supply pressure is 10Bar
3. Operating Temperature
Standard:-20℃~+80℃
Low temperature:-35℃~+80℃(can be customized)
High temperature:-15℃~+150℃(can be customized)
4. Travel Adjustment
Have adjustment range of ±5°for the rotation at 0°and 90°
5. Application
Either indoor or outdoor
|